ERCES code adoption, any locally published trigger, and AHJ contacts for Plano, Texas. Sourced from Zion's internal jurisdiction database and last verified September 2026.
| Adopted IFC edition | 2024 IFC |
|---|---|
| NFPA 72 edition referenced | 2019 NFPA 72 |
| NFPA 1225 referenced | Yes |
| ERCES trigger — square footage | exceeding 12,000 sq ft (per published policy) |
| ERCES trigger — stories above grade | No local story threshold on file |
| Signal threshold | -95 dBm |
| DAQ requirement | DAQ 3.4 |
| Battery backup | 12 hrs |
| Annual inspection | Required |
| Submittal portal | Plano Online Portal |
| ERCC permit required | Yes |
| Plan review timeline | 3–5 weeks |
| Fire Marshal contact | Plano Fire-Rescue: 972-941-7100 |
| Radio shop coordination | Radio Shop: 972-941-5080 |
| Enforcement level | Very High |
| Last verified | September 2026 |
STRICT: DAQ 3.4 (not 3.0); P-25 800 MHz only; separate radio-shop frequency letter; 26-item checklist; GROL + NICET IB-PSC required; supervisor must witness acceptance test